Chapter 27 UTILITIES*
Section 27-104 Motor installations.
(a) Electric motors larger than ten (10) horsepower shall
be three-phase, except by special
approval of the director.
(b) The starting current for any three-phase motor shall
not exceed eight (8) per cent of the full
load capacity for the department's distribution feeder which serves the motor. The maximum size
motor which will be permitted to start across the line without current limiting starters for various
feeder voltages, is as follows:
|
2,400
volt
feeder....
|
25
horsepower
|
|
13,800
volt
feeder....
|
150
horsepower
|
(Code 1964, § 15.520)