Chapter 9 FIRE PREVENTION AND PROTECTION*
Section 9-22 Amendments.
The code adopted by this article is hereby amended by substituting the following
sections in
lieu of those sections with corresponding numbers in the 2009 edition of the International Fire
Code, or where there is no corresponding section in the code; the following sections shall be
enacted as additions to the code:
101.1 Title: These regulations shall be known as the Fire Code of Columbia, Missouri,
and
hereinafter referred to as "this code."
Section 103.0 Fire Prevention
103.1 Director:
The administration and enforcement of this ordinance shall be the duty of the
director of
community development
and the fire chief, who are hereby authorized to take such
action as may be reasonably necessary to enforce the provisions of this code. Such persons may
be appointed and authorized as assistants or representatives of the director and the chief as may
be necessary to carry out the provisions of this code.
103.2: Appointment: Delete
103.4 Relief from personal responsibility: the code official, officer or employee charged with the
enforcement of this code, while acting for the jurisdiction, shall not thereby be rendered liable
personally, and is hereby relieved from all personal liability for any damage accruing to persons
or property as a result of any act required or permitted in the discharge of official duties. Any suit
instituted against any officer of employee because of an act performed by that officer or
employee in the lawful discharge of duties and under the provisions of this code shall be
defended by the legal representative of the jurisdiction until the final termination of the costs in
any action, suit or proceeding that is instituted in pursuance of the provisions of this code; and
any officer of the building and site development division or the fire department acting in good
faith and without malice, shall be free from liability for acts performed under any of its
provisions or by reason of any act or omission in the performance of official duties in connection
therewith.
105.6.47 Fire Performance Art. An operational permit is required to use open flames defined as
Fire Performance Art under amended code section 316.
105.7 Required construction permits. The building code official is authorized to issue
construction permits for work as set forth in Sections 105.7.1 through 105.7.13.
108.1 Application for Appeal: Any aggrieved person shall have the right to appeal a decision of
the code official to the Building Construction Codes Commission (BCCC). An application for
appeal shall be filled in accordance with the procedures set out in section 112 of the 2009 edition
of the International Building Code as amended by section 6-17 of the Code of Ordinances. The
application shall be filed on a form obtained from the code official.
108.2 Limitation on authority: Delete.
108.3 Qualifications: Delete.
109.3 Violation penalties: Any person who shall violate a provision of this code or shall fail to
comply with any of the requirements thereof, shall be guilty of a misdemeanor and upon
conviction thereof, shall be punished by a fine of not more than one thousand dollars ($1,000.00)
or by imprisonment not exceeding one (1) year, or by both such fine and imprisonment. Each day
that a violation continues shall be deemed a separate offense.
111.4 Failure to comply: Delete.
308.1.4 Open-flame cooking devices - Charcoal burner and other open flame cooking devices
shall not be operated on combustible balconies or within ten (10) feet of combustible
construction.
Exceptions:
1. One-and-two family dwellings.
2. Apartment buildings and condominiums.
3. Where buildings, balconies and decks are protected by an automatic sprinkler
system.
313.3 Fire Sprinklers. A builder of single family dwellings or residences or multi-unit dwellings
of four (4) or fewer units shall offer to any purchaser on or before the time of entering into the
purchase contract the option, at the purchasers cost, to install or equip fire sprinklers in the
dwelling, residence, or unit. Notwithstanding any other provision of the law to the contrary, no
purchaser of such a single family dwelling, residence, or multi-unit dwelling shall be denied the
right to choose or decline to install a fire sprinkler system in such dwelling or residence being
purchased by any code, ordinance, rule, regulation, order, or resolution by any county or other
political subdivision. Any county or other political subdivision shall provide in any such code,
ordinance, rule, regulation, order, or resolution the mandatory option for a purchaser to have the
right to choose and the requirement that offers to the purchaser the option to purchase fire
sprinklers in connection with the purchase of any single family dwelling, residence, or multi-family
dwelling of four (4) or fewer units.
315.3.2 Height. Storage in the open shall not exceed twenty (20) feet (6096 mm) in height.
Section
318
Fire Performance Art
31
8
.1 General. Fire Performance Art shall be defined as any act (fire juggling, fire eating, etc.) in
a public or private place, which utilizes fire for entertainment purposes, outside of a protective
housing or in ways in which it travels through the air (by one person or multiple persons). These
acts do not include pyrotechnics or other open flame devices as regulated by other code sections
or permits.
31
8
.2 Permits. A permit in accordance with 105.6.33 shall be secured from the fire code official
prior to the date of the fire performance art taking place.
31
8
.3 Space considerations. A ten (10) foot distance shall be maintained between the fire-involved item
and the any member of an audience, any combustible decoration, and any
combustible item within the immediate performance area. A minimum ten (10) foot ceiling
height is required.
31
8
.4 Extinguishing Agents. At minimum, one (1) 2A-10BC multipurpose fire extinguisher shall
be required for every five (5) performers at each performance. Additional fire extinguishers may
be required by the code official based upon the unique circumstances of the performance and
occupancy.
31
8
.4.1 One (1) wet towel for each active fire performer shall be provided to extinguish the fire
implement. The towel shall be white in color to differentiate its use from other colors that may be
used to clean up flammable or combustible liquid spills. Towels used for cleaning up flammable
or combustible liquid spills shall be stored in a metal container with a tight fitting lid.
31
8
.4.2 One (1) listed fire blanket shall be provided for every five (5) performers.
31
8
.5 Personal Safety. A five (5) gallon open-topped bucket of water will be provided for each
fire performance area.
31
8
.5.1 Spotter. One (1) trained spotter shall be provided for each performance. The spotter shall
be positioned between the active fire performer and the audience. Spotters should be trained in
the proper use of fire extinguishers. The spotter may be a performer who is not engaged in the
current performance. The fire code official may require additional spotters based on the unique
circumstances of the performance and occupancy.
31
8
.6 Fuels. Approved common fuels used for fire performance art include:
Denatured alcohol;
Lamp oil (odorless and smokeless);
Kerosene (for outdoor performances only);
Stove Fuel;
"Shell Sol T" brand fuel;
"Allume Fue" brand fuel;
"Fire Water" brand fuel;
Gasoline is prohibited under any circumstances.
31
8
.6.1 Fuel Quantities and Storage. All fuels shall be stored in their original container(s) with
the caps in place when not in use. The maximum quantity of fuel on the site shall be one (1) U.S.
gallon per performer.
31
8
.7 Wicks. Wick material shall consist of cotton wrapped in Kevlar to prevent the breakdown
of the cotton as it burns. Synthetic wick material shall be avoided.
31
8
.8 Clothing. It is recommended that the clothing worn by the performers be made of fire
resistive materials such as natural fibers or Nomex/PBI.
31
8
.9 Smoking. Smoking is prohibited by within fifty (50) feet of the performance area and fuel
storage. No smoking signs shall be posted accordingly.
505.1.2 (add the words) Each exterior egress doorway on a building shall have a letter affixed to
upper left hand corner of the exterior face of the door beginning with the main entrance door
and
working clockwise around the building. The letters shall be of a reflective material, blue in color,
a minimum of six (6) inches tall with a minimum stroke of one-half (0.5) inches.
507.3 Fire Flow. Fire hydrants in areas zoned as single family or duplex shall be spaced no
greater than every five hundred (500) feet and shall be capable of flowing a minimum of eight
hundred (800) gallons of water per minute for a minimum of four (4) hours. In all other areas,
fire hydrants shall be spaced no greater than every three hundred (300) feet and shall be capable
of flowing a minimum of one thousand five hundred (1,500) gallons of water per minute for a
minimum of four (4) hours; as measured by an approved route around the exterior of the facility
or building, onsite fire hydrants and mains shall be provided where required by the code official.
507.5.1 Delete
510.1 Emergency responder radio coverage in buildings shall be provided in all new high-rise
buildings and other buildings specifically required by the authority having jurisdiction based on
known substantiated problems associated with radio coverage.
609.4 Existing fire suppression systems not meeting the UL 300 criteria shall be upgraded to UL
300 compliant systems within three (3) years of the adoption of this code.
704.1 Enclosure. (Add exception)
Exception: Where any structure has previously received a certificate of compliance or a
certificate of occupancy has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary power from
the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over current
protection.
c. All smoke detectors in shafts and corridors, if such exist, shall be interconnected
such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
d. Any structure in compliance with the provisions of section 704.1 shall maintain
such
compliance.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
903.2.1.2 Group A-2. An automatic fire sprinkler system shall be provided for Group A-2
occupancies where one of the following conditions exists:
1. The fire area exceeds five thousand (5,000) square
feet (465m2);
2. The fire area has an occupancy load of two hundred
(200) or more; or
3. The fire area is located on a floor other than the
level of exit discharge.
903.4.2 (Add the words) Alarms. A combination horn strobe shall be installed on the exterior of
the building above the Fire Department Connection (FDC) on all sprinkler systems.
903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings
containing a Group M occupancy where one of the following conditions exists: Delete number
4.
903.2.8.1 Fraternity and Sorority Houses. Each fraternity and sorority house and fraternity and
sorority annex with sixteen (16) or more occupants existing on March 16, 2009 shall install at a
minimum an automatic fire sprinkler system, designed and installed under the current edition of
the National Fire Protection Association Standard 13R, in accordance with Section 903.3 of the
2006 International Fire Code, no later than March 16, 2016.
New fraternity and sorority houses and fraternity and sorority annexes and such houses and
annexes that undergo renovation of their space, shall install at a minimum an NFPA 13R fire
sprinkler system.
The city council may vary the requirements of this section for any fraternity or sorority house the
owners of which have been unable to comply with this section despite making good faith efforts
to do so.
For purposes of this section, fraternity and sorority house means any building used as a
dwelling and occupied by and maintained exclusively or primarily for college, university or
professional school students who are affiliated with a social, honorary or professional
organization recognized currently or in the past by a college, university or professional school
903.6.2 Group I-2. An automatic sprinkler system shall be provided throughout Group I-2 fire
areas where required in Chapter 46.
912.3.1 (Add the words) Locking fire department connection caps. Fire department connections
(FDC) shall be a four (4) inch Stroz connection and shall utilize a Knox locking FDC cap.
1011.1 Illuminated Exit Signs - Where required. (Add the words)
Illuminated exit signs in A1, A2, R-1 and R-2 use groups shall be placed above exit doors and to
the side of exit doors eighteen (18) inches from the floor. The floor level exit signs shall be
protected by a guard to prevent physical damage. This amendment shall not be retroactive in
nature, and shall not apply to structures prior to January 1, 2007.
1011.5.2 Exit sign illumination. (Add the words)
Internally illuminated exit signs shall not use incandescent light bulbs relying upon a filament for
the source of illumination. This amendment shall be applicable under the following conditions:
In all new and remodeled construction where illuminated exit signs are required or provided; and
when exit signs are replaced or deemed inoperable by the jurisdiction having authority; and
where an exit sign is installed in new locations in existing buildings, upon order of the City Fire
Marshall.
This amendment shall not be retroactive in nature, and shall not apply to structures constructed
prior to January 1, 2003.
1018.1 Corridors (add exception)
Exception. Where any structure has previously received a certificate of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and
corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their
primary power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over-current
protection.
c. All smoke detectors in shafts and corridors, if such
exist, shall be interconnected such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
1020. 1 General. (add exception)
Exception. Where any structure has previously received a certificate of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and
corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their
primary power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over-current
protection.
c. All smoke detectors in shafts and corridors, if such
exist, shall be interconnected such that
the actuation of one alarm will actuate all alarms in the shafts and corridors.
d. Existing windows in a sleeping room shall not be eliminated.
1021.2 Buildings with one exit. (add exception)
Where any structure has previously received a certification of compliance or a certificate of
occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and
corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their
primary power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over-current
protection.
c. All smoke detectors in shafts and corridors, if such
exist, shall be interconnected such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
3301.1.3 Fireworks. The manufacture, storage, sale and use of fireworks are prohibited, except
where allowed under section 16-234 of the Code of Ordinances.
B105.1 One and Two Family Dwellings. The minimum fire flow requirements for one and
two
family dwellings having a fire area which does not exceed three thousand six hundred (3,600)
square feet (344m2) shall be eight hundred (800) gallons per minute (3785L/min) for a minimum
of four (4) hours.
B105.2 Buildings other then one and two family dwellings. The minimum fire flow and flow
duration for buildings other then one and two family dwelling units shall be one thousand five
hundred (1,500) gallons per minute for a minimum of four (4) hours. The code official may use
table B105.1 to determine fire flows under special circumstances.
C105.1 Fire Hydrant spacing. Fire hydrants shall have a maximum spacing of 500 feet in all R-1
(Single family) and R-2 (Duplex) developments and 300 feet in all other zoning districts. Fire
hydrant spacing for buildings that are required by the 2006 edition of the International Building
Code to have a fire flow greater than or equal to 6,000 gallons per minute shall be regulated by
Table C105.1
C105.1.2 Fire hydrant spacing. A fire hydrant capable of flowing a minimum of one thousand
five hundred (1,500) gallons per minute for a minimum of four (4) hours shall be placed within
one hundred (100) feet of any fire department connection (FDC). This hydrant shall be placed so
that it does not impede access to the building or area by responding fire department equipment.
(Ord. No. 14121, § 1, 7-5-94; Ord. No. 15211, § 1, 4-21-97; Ord. No. 15400,
§ 1, 10-20-97; Ord.
No. 17507, § 1, 11-4-02; Ord. No. 19358; § 1, 1-2-07; Ord. No. 20209, § 1, 3-16-09; Ord.
No.
20913, § 1, 3-21-11; Ord. No. 21095, § 3, 9-19-11; Ord. No. 21201, § 1, 1-3-12)
(Ord. 21201, Amended, 01/03/2012, Prior Text; Ord. 21095, Amended, 09/19/2011, Prior Text; Ord. 20913, Amended, 03/21/2011, Prior Text; Ord. 20209, Amended, 03/16/2009, Prior Text; Ord. 19358, Amended, 01/02/2007, Prior Text; Ord. 17507, Amended, 11/04/2002, Prior Text)