Section 9-22 Amendments.
Prior to the adoption of Ord. 19358 on 01/02/2007, Section 9-22 read as follows.
The code adopted by this article is hereby amended by substituting the following sections in
lieu of those sections with corresponding numbers in the 2000 edition of the International Fire
Code, or, where there is no corresponding section in the code, the following sections shall be
enacted as additions to the code:
101.1 Title: These regulations shall be known as the Fire
Code of Columbia, Missouri, and
hereinafter referred to as this code.
Section 103.0 Fire Prevention
103.1 Director: The administration and enforcement of this ordinance shall
be the duty of the
director of public works and the fire chief, who are hereby authorized to take such action as may
be reasonably necessary to enforce the provisions of this code. Such persons may be appointed
and authorized as assistants or representatives of the director and the chief as may be necessary
to carry out the provisions of this code.
103.2: Appointment: Delete
103.4 Relief from personal responsibility: The code official, officer or employee
charged with
the enforcement of this code, while acting for the jurisdiction, shall not thereby render himself
liable personally, and is hereby relieved from all personal liability for any damage accruing to
persons or property as a result of any act required or permitted in the discharge of official duties.
Any suit instituted against any officer or employee because of an act performed by that officer or
employee in the lawful discharge of duties and under the provisions of this code shall be
defended by the legal representative of the jurisdiction until the final termination of the
proceedings. The code official or any subordinate shall not be liable for costs in any action,
suit
or proceeding that is instituted in pursuance of the provisions of this code; and any officer of the
protective inspection division or the fire department acting in good faith and without malice,
shall be free from liability for acts performed under any of its provisions or by reason of any act
or omission in the performance of official duties in connection therewith
108.1 Application for Appeal: Any aggrieved person shall
have the right to appeal a decision
of the code official to the building construction codes commission. An application for appeal
shall be filed in accordance with the procedures set out in Section 112 of the 2000 edition of
the
International Building Code as amended by Section 6-17 of the Code of Ordinances. The
application shall be filed on a form obtained from the code official.
Delete 108.2 and 108.3.
109.3 Violation penalties. Any person who shall violate
a provision of this code or shall fail to
comply with any of the requirements thereof, shall be guilty of a misdemeanor and upon
conviction thereof, shall be punished by a fine of not more than one thousand dollars ($1,000) or
by imprisonment not exceeding one year, or by both such fine and imprisonment. Each day that
a violation continues shall be deemed a separate offense.
Delete 111.4.
307.5 Open-flame cooking devices . Charcoal burner and other open flame cooking devices
shall
not be operated on combustible balconies or within 10 feet of combustible construction.
Exceptions:
1. One- and two-family dwellings
2. Apartment buildings and condominiums
3. Where buildings and decks are protected by an automatic sprinkler
system
609.1 Hood system required: Each existing commercial cooking appliance and domestic
cooking
appliance utilized for commercial cooking purposes shall be protected with an approved
commercial kitchen exhaust hood and duct system
Exceptions:
1. Cooking appliances located within a dwelling unit and not
utilized for commercial purposes.
2. Completely
enclosed ovens.
3. Steam tables
4. Auxiliary
cooking equipment that does not produce grease laden vapors, including
toasters, coffee makers and egg cookers
Delete 609.1.1
609.2 Hood system suppression: Each existing required commercial kitchen exhaust hood
and
duct system shall be protected with an approved automatic fire suppression system installed in
accordance with the mechanical code listed in Chapter 45.
Delete 609.2.1
Delete 609.2.2
Delete 609.2.3
609.3 Maintenance: Commercial kitchen exhaust systems shall be cleaned to remove deposits
of
residue and grease in the system at intervals specified in the cleaning schedule required to be
submitted in accordance with the mechanical code listed in Chapter 45. Thorough cleaning of
ducts, hoods and fans shall require scraping, brushing or other positive cleaning methods. Where
a cleaning schedule is not on file, the code official shall require a schedule to be submitted,
indicating the method of cleaning and the time intervals between cleaning.
Delete 609.3.1, 609.3.2, 609.3.3, 609.3.4 609.5, 609.6, 609.7 and 609.7.1
704.1 Enclosure. (add exception)
Exception: Where any structure has previously received
a certificate of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors,
if such exist.
b. Shaft and
corridor smoke detectors shall receive their primary power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for overcurrent
protection.
c. All smoke
detectors in shafts and corridors, if such exist, shall be interconnected such
that the actuation of one alarm will actuate all the alarms in the shafts and corridors.
d. Any structure
in compliance with the provisions of section 704.1 shall maintain such
compliance.
This exception shall not apply to structures that are renovated, remodeled or altered
in excess of
fifty (50) percent of the current value of the structure.
1003.2.10.4 Exit sign illumination. (add the words)
Internally illuminated exit signs shall not use incandescent light bulbs relying upon
a filament for
the source of illumination. This ammendment shall be applicable under the following conditions:
In all new and remodeled construction where illuminated exit signs are required or provided;
and
when exit signs are replaced or deemed inoperable by the jurisdiction having authority; and
where an exit sign is installed in new locations in existing buildings, upon order of the City Fire
Marshall.
This ammendment shall not be retroactive in nature, and shall not apply to structures
prior to
January 1, 2003.
1005.2.2 Buildings with one exit. (add exception)
. . .
4. Where any structure has previously
received a certificate of compliance or a certificate of
occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors,
if such exist.
b. Shaft and
corridor smoke detectors shall receive their primary power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for overcurrent
protection.
c. All smoke
detectors in shafts and corridors, if such exist, shall be interconnected such
that the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception 4 shall not apply to structures that are renovated, remodeled or altered
in excess
of fifty (50) percent of the current value of the structure.
1009.1 General. (add exception)
. . .
5. Where any structure has previously
received a certificate of compliance or a certificate of
occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors
shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary
power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for overcurrent
protection.
c. All smoke detectors in shafts and corridors, if such exist,
shall be interconnected such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
d. Existing windows in a sleeping room shall not be eliminated.
This exception 5 shall not apply to structures that are renovated, remodeled or altered
in excess
of fifty (50) percent of the current value of the structure.
1010.17 Corridors. (add exception)
5. Where any structure has previously received a certificate of compliance or
a certificate of
occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors,
if such exist.
b. Shaft and corridor smoke detectors shall receive their primary
power from the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for overcurrent
protection.
c. All smoke
detectors in shafts and corridors, if such exist, shall be interconnected such
that the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception 5 shall not apply to structures that are renovated, remodeled or altered
in excess
of fifty (50) percent of the current value of the structure.
3301.1.3 Fireworks. The manufacture, storage, sale and
use of fireworks are prohibited, except
where allowed under Section 16-234 of the Code of Ordinances.
B105.1 One and Two Family Dwellings. The minimum fire flow requirements for one
and two
family dwellings having a fire area which does not exceed 3,600 square feet (344m2) shall be
800 gallons per minute (3785L/min).
C102.2 Fire hydrant location. A fire hydrant shall be located within 100 feet of a fire
department
automatic sprinkler fire suppression system connection, a water fire suppression standpipe or
where required by the code official.
C105.1 Distribution of Fire Hydrants. Fire hydrants shall have a maximum spacing
of 500 feet in
all R-1 (Single family) and R-2 (Duplex) developments and 300 feet in all other zoning districts.
Fire hydrant spacing for buildings that are required by the 2000 edition of the International
Building Code to have a fire flow greater than or equal to 6,000 gallons per minute shall be
regulated by Table C105.1.
(Ord. No. 14121, § 1, 7-5-94; Ord. No. 15211, § 1, 4-21-97; Ord. No. 15400, § 1, 10-20-97;
Ord.
No. 17507, § 1, 11-4-02)