Series 108 2007 ORDINANCES/RESOLUTIONS
Section 108-022; Ord. 19358; Repealing Article II of Chapter 9 of the City Code relating to the 2000 Edition of the International Fire Code and enacting in lieu thereof a new Article II adopting the 2006 Edition of the International Fire Code
Ordinance No. 19358 Council
Bill No. B 515-06
AN ORDINANCE
repealing Article II of Chapter 9 of the City Code relating to the 2000 Edition of the International
Fire Code and enacting in lieu thereof a new Article II adopting the 2006 Edition of the
International Fire Code; and fixing the time when this ordinance shall become effective.
BE IT ORDAINED BY THE COUNCIL OF THE CITY OF COLUMBIA, MISSOURI AS
FOLLOWS:
SECTION 1. Article II of Chapter 9 of the Code of Ordinances.
City of Columbia, Missouri,
relating to the 2000 Edition of the International Fire Code, is hereby repealed and in lieu thereof
a new Article II, relating to the 2006 Edition of the International Fire Code, is hereby enacted
reading in words and figures as follows:
CHAPTER 9. FIRE PREVENTION AND PROTECTION
. . .
Article II FIRE CODE
Sec. 9-21 Adoption
The 2006 Edition of the International Fire Code published by the International
Code Council,
Inc., including Appendices B, C, D, E, F and G, three copies of which have been on file with the
City Clerk for a period of ninety (90) days prior to the adoption of this article, is hereby adopted
by reference and made a part of the Code of Ordinances, City of Columbia, Missouri as fully as
if set forth in its entirety. At least three (3) copies of the 2006 Edition of the International Fire
Code shall remain on file in the office of the City Clerk and shall be kept available for public
use, inspection and examination.
Sec. 9-22 Amendments
The code adopted by this article is hereby amended by substituting the following
sections in
lieu of those sections with corresponding numbers in the 2006 Edition of the International Fire
Code, or where there is no corresponding section in the code, the following sections shall be
enacted as additions to the code:
101.1 Title: These regulations shall be known as the Fire Code of Columbia, Missouri, and
hereinafter referred to as "this code."
Section 103.0 Fire Prevention
103.1 Director: The administration and enforcement of this ordinance shall be the duty of the
director of public works and the fire chief, who are hereby authorized to take such action as may
be reasonably necessary to enforce the provisions of this code. Such persons may be appointed
and authorized as assistants or representatives of the director and the chief as may be necessary
to carry out the provisions of this code.
103.2 Appointment: Delete
103.4 Relief from personal responsibility: the code official, officer or employee charged with the
enforcement of this code, while acting for the jurisdiction, shall not thereby be rendered liable
personally, and is hereby relieved from all personal liability for any damage accruing to persons
or property as a result of any act required or permitted in the discharge of official duties. Any suit
instituted against any officer of employee because of an act performed by that officer or
employee in the lawful discharge of duties and under the provisions of this code shall be
defended by the legal representative of the jurisdiction until the final termination of the costs in
any action, suit or proceeding that is instituted in pursuance of the provisions of this code; and
any officer of the protective inspection division or the fire department acting in good faith and
without malice, shall be free from liability for acts performed under any of its provisions or by
reason of any act or omission in the performance of official duties in connection therewith.
105.6.33 Fire performance art. An operational permit is required to use open flames defined as
fire performance art under section 316 of this code.
105.7 Required construction permits. The building code official is authorized to issue
construction permits for work as set forth in sections 105.7.1 through 105.7.13.
108.1 Application for Appeal: Any aggrieved person shall have the right to appeal a decision of
the code official to the Building Construction Codes Commission (BCCC). An application for
appeal shall be filled in accordance with the procedures set out in Section 112 of the Building
Code of Columbia, Missouri. The application shall be filed on a form obtained from the code
official.
108.2 Limitations on Authority: Delete
108.3 Qualifications: Delete
109.3 Violation penalties: Any person who shall violate a provision of this code or shall fail to
comply with any of the requirements thereof, shall be guilty of a misdemeanor and upon
conviction thereof, shall be punished by a fine of not more than one thousand dollars ($1,000) or
by imprisonment not exceeding one year, or by both such fine and imprisonment. Each day that a
violation continues shall be deemed a separate offense.
111.4 Failure to Comply: Delete
308.3.1 Open-flame cooking devices - Charcoal burner and other open flame cooking devices
shall not be operated on combustible balconies or within 10 feet of combustible construction.
Exceptions:
1. One- and two-family dwellings.
2. Apartment buildings and condominiums.
3. Where buildings, balconies and decks are protected by an automatic sprinkler
system.
Section 316 Fire Performance Art
316.1 General. Fire Performance Art shall be defined as any act (fire juggling, fire eating, etc.) in
a public or private place, which utilizes fire for entertainment purposes, outside of a protective
housing or in ways in which it travels through the air (by one person or multiple persons). These
acts do not include pyrotechnics or other open flame devices as regulated by other code sections
or permits.
316.2 Permits. A permit in accordance with 105.6.33 shall be secured from the fire code official
prior to the date of the fire performance art taking place.
316.3 Space considerations. A ten (10) foot distance shall be maintained between the fire-involved item
and any member of an audience, any combustible decoration, and any combustible
item within the immediate performance area. A minimum ten (10) foot ceiling height is required.
316.4 Extinguishing Agents. At minimum, one (1) 2A-10BC multipurpose fire extinguisher shall
be required for every five (5) performers at each performance. Additional fire extinguishers may
be required by the code official based upon the unique circumstances of the performance and
occupancy.
316.4.1 One wet towel for each active fire performer shall be provided to extinguish the fire
implement. The towel shall be white to differentiate its use from other colors that may be used to
clean up flammable or combustible liquid spills. Towels used for cleaning up flammable or
combustible liquid spills shall be stored in a metal container with a tight fitting lid.
316.4.2 One listed fire blanket shall be provided for every five (5) performers.
316.5 Personal Safety. A five gallon open-topped bucket of water will be provided for each fire
performance area.
316.5.1 Spotter. One trained spotter shall be provided for each performance. The spotter shall be
positioned between the active fire performer and the audience. Spotters should be trained in the
proper use of fire extinguishers. The spotter may be a performer who is not engaged in the
current performance. The fire code official may require additional spotters based on the unique
circumstances of the performance and occupancy.
316.6 Fuels. Approved common fuels used for fire performance art include:
Denatured Alcohol
Lamp Oil (odorless and smokeless)
Kerosene (For outdoor performances only)
Stove Fuel
"Shell Sol T" brand fuel
"Allume Fue" brand fuel
"Fire Water" brand fuel
Gasoline is prohibited under any circumstances.
316.6.1 Fuel Quantities and Storage. All fuels shall be stored in their original container(s) with
the caps in place when not in use. The maximum quantity of fuel on the site shall be one (1) U.S.
gallon per performer.
316.7 Wicks. Wick material shall consist of cotton wrapped in Kevlar to prevent the breakdown
of the cotton as it burns. Synthetic wick material shall be avoided.
316.8 Clothing. It is recommended that the clothing worn by the performers be made of fire
resistive materials such as natural fibers or Nomex/PBI.
316.9 Smoking. Smoking is prohibited by within fifty (50) feet of the performance area and fuel
storage. No smoking signs shall be posted accordingly.
505.1.2 (add the words) Each exterior egress doorway on a building shall have a letter affixed to
upper left hand corner of the exterior face of the door beginning with the main entrance door
and
working clockwise around the building. The letters shall be of a reflective material, blue in color,
a minimum of six (6) inches tall with a minimum stroke of 0.5 inches.
508.3 Fire Flow. Fire hydrants in areas zoned as single family or duplex shall be spaced no
greater than every five hundred (500) feet and shall be capable of flowing a minimum of eight
hundred (800) gallons of water per minute for a minimum of four (4) hours. In all other areas,
fire hydrants shall be spaced no greater than every three hundred (300) feet and shall be capable
of flowing a minimum of 1,500 gallons of water per minute for a minimum of four (4) hours; as
measured by an approved route around the exterior of the facility or building, on site fire
hydrants and mains shall be provided where required by the code official.
508.5.1 Delete
609.2 Hood system required: Each existing commercial cooking appliance and domestic cooking
appliance utilized for commercial cooking purposes shall be protected with an approved
commercial kitchen hood and duct system.
Exceptions:
1. Cooking appliances located within a dwelling unit and not utilized for commercial
purposes.
2. Completely enclosed ovens.
3. Steam tables
4. Auxiliary cooking equipment that does not produce grease laden vapors, including
toasters,
coffee makers and egg cookers.
609.3 Hood system suppression: Each existing required commercial kitchen exhaust hood and
duct system shall be protected with an approved automatic fire suppression system installed
in
accordance with the 2006 International Mechanical Code.
609.4 Maintenance: Commercial kitchen exhaust systems shall be cleaned to remove deposits of
residue and grease in the system at intervals specified in the cleaning schedule required to be
submitted in accordance with the 2006 International Mechanical Code. Thorough cleaning of
ducts, hoods and fans shall require scraping, brushing or other positive cleaning methods. Where
a cleaning schedule is not on file, the code official shall require a schedule to be submitted,
indicating the method of cleaning and the time intervals between cleaning.
609.5 Existing fire suppression systems not meeting the UL 300 criteria shall be upgraded to UL
300 compliant systems within three (3) years of the adoption of this code and, with written
notification by the fire department after inspection.
704.1 Enclosure. (add exception)
Exception: Where any structure has previously received a certificate of compliance or a
certificate of occupancy has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary power from
the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over current
protection.
c. All smoke detectors in shafts and corridors, if such exist, shall be interconnected
such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
d. Any structure in compliance with the provisions of section 704.1 shall maintain
such
compliance.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
903.2.1.2 Group A-2: Item 2. The fire area has an occupant load of 200 or more; or
903.2.7.1 Fraternity and Sorority Houses. An automatic fire sprinkler system installed in
accordance with Section 903.3 shall be provided in all existing fraternity and sorority houses by
December 31, 2012.
1. Year one, 2007, will be used to plan the installation
of sprinkler systems.
2. Years one and two, 2007 and 2008, will be used acquire and appropriate needed
funds.
3. Years three through five, 2009, 2010 and 2011, will be used to engineer and
install fire
sprinkler systems.
903.4.2 (add the words) Alarms. A combination horn strobe shall be installed above the Fire
Department Connection (FDC) on all sprinkler systems.
912.3.1 (add the words) Locking fire department connection caps. Fire department connections
(FDC) shall be a four (4) inch Stroz connection and shall utilize a Knox locking FDC cap.
1011.1 Illuminated Exit Signs - Where required. (add the words)
Illuminated exit signs in A1, A2, R-1 and R-2 use groups shall be placed above exit doors and to
the side of exit doors 18 inches from the floor. The floor level exit signs shall be protected by a
guard to prevent physical damage. This provision shall not be retroactive in nature, and shall not
apply to structures constructed prior to January 1, 2007.
1011.5.2 Exit sign illumination. (add the words)
Internally illuminated exit signs shall not use incandescent light bulbs relying upon a filament for
the source of illumination. This amendment shall be applicable under the following conditions:
In all new and remodeled construction where illuminated exit signs are required or provided: and
when exit signs are replaced or deemed inoperable by the jurisdiction having authority; and
where an exit sign is installed in new locations in existing buildings, upon order of the City fire
marshal.
This provision shall not be retroactive in nature, and shall not apply to structures constructed
prior to January 1, 2003.
1017.1 Corridors (add exception)
Exception. Where any structure has previously received a certificate of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary power from
the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over current
protection.
c. All smoke detectors in shafts and corridors, if such exist, shall be interconnected
such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
1019.2 Buildings with one exit. (add exception)
Where any structure has previously received a certification of compliance of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary power from
the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over current
protection.
c. All smoke detectors in shafts and corridors, if such exist, shall be interconnected
such that
the actuation of one alarm will actuate all the alarms in the shafts and corridors.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
1020. 1 General. (add exception)
Exception. Where any structure has previously received a certificate of compliance or a
certificate of occupancy, has been maintained accordingly and complies with the following:
a. Smoke detectors shall be installed in all shafts and corridors, if such exist.
b. Shaft and corridor smoke detectors shall receive their primary power from
the building
wiring and when primary power is interrupted, shall receive power from a battery. Wiring shall
be permanent and without a disconnecting switch other than those required for over current
protection.
c. All smoke detectors in shafts and corridors, if such exist, shall be
interconnected such that
the actuation of one alarm will actuate all alarms in the shafts and corridors.
d. Existing windows in a sleeping room shall not be eliminated.
This exception shall not apply to structures that are renovated, remodeled or altered in excess of
fifty (50) percent of the current value of the structure.
3301.1.3 Fireworks. The manufacture, storage, sale and use of fireworks are prohibited, except
where allowed under Section 16-234 of the Code of Ordinances.
B105.1 One and Two Family Dwellings. The minimum fire flow requirements for one- and two-family
dwellings having a fire area which does not exceed 3,600 square feet (344m2) shall be
eight hundred (800) gallons per minute (3785L/min) for a minimum of four (4) hours.
B105.2 Buildings other then one- and two-family dwellings. The minimum fire flow and flow
duration for buildings other then one and two-family dwelling units shall be 1,500 gallons
per
minute for a minimum of four (4) hours. The code official may use table B105.1 to determine fire
flows under special circumstances.
C105.1 Fire Hydrant spacing. Fire hydrants shall have a maximum spacing of five hundred (500)
feet in all R-1 (single family) and R-2 (duplex) zoning districts and three hundred (300) feet in
all other zoning districts. Fire hydrant spacing for buildings that are required by the 2006 edition
of the International Building Code to have a fire flow greater than or equal to 6,000 gallons per
minute shall be regulated by Table C105.1
C105.1.2 Fire hydrant spacing. A fire hydrant capable of flowing a minimum of 1,500 gallons per
minute for a minimum of four (4) hours shall be placed within one hundred (100) feet of any fire
department connection (FDC). This hydrant shall be placed so that it does not impede access to
the building or area by responding fire department equipment.
SECTION 2. The repeal of Article II of Chapter 9 of the
Code of Ordinances, City of
Columbia, Missouri, relating to the 2000 Edition of the International Fire Code, shall not affect
any offense or act committed or done or any penalty or forfeiture incurred before the effective
date of this ordinance.
SECTION 3. This ordinance shall be in full force and
effect from and after April 2, 2007.
PASSED this 2nd day of January, 2007.